Description: Square body flush
end contact high speed fuses.
Dimensions: See dimensions
illustrations.
Ratings:
Volts: — 690Vac (IEC)
— 700Vac (UL)
Amps: — 40-2000A IR: — 200kA RMS Sym.
Agency Information: CE, Designed and tested to IEC
60269: Part 4, UL Recognized. Consult Cooper Bussmann
for UL Recognition / CSA Component Acceptance Status.
Electrical Characteristics
Total Clearing I2t
The total clearing I2t at 1.5rated voltage and at power
factor of 15% are given in 1.0the electrical
characteristics. For other
voltages, the clearing I2t is
found by multiplying by
correction factor, K, given
as a function of applied
working voltage, Eg, (rms).
Arc Voltage
This curve gives the peak
arc voltage, U , which 103
may appear across the
fuse during its operation
as a function of the
applied working voltage,
Eg, (rms) at a power factor
of 15%.
Power Losses
Watts loss at rated current
is given in the electrical
characteristics. The curve
allows the calculation of
the power losses at load
currents lower than the
rated current. The
correction factor, Kp, is
given as a function of the
RMS load current, Ib, in %
of the rated current.
Features and Benefits
• Excellent DC performance
• Low arc voltage and low energy let-through (I2t)
• Low watts loss
• Superior cycling capability
Typical Applications
• DC common bus
• DC drives
• Power converters/rectifiers
• Reduced voltage starters
or Other Voltage Ratings in This Body Style
• See pages 148 (1000V) and 162 (1250V/1300V)
Dimensions (mm) B
Type -B/-, -BKN/-, -G/-, -GKN/-
**Valid for fuses type -G/- & -GKN/-.
NB: B = 65 for: Size 2, 1100-1250A
Size 3, 1600-2000A
1mm = 0.0394” / 1” = 25.4mm
Catalog Numbers
†Rated voltage (IEC) 600V. ‡Rated voltage (IEC) 550V. • Watts loss provided at rated current. • Microswitch indicator ordered separately. See accessories on pages 185-186.
• For fuse curves see pages 130 and 131.