Description: Square body flush
end contact high speed fuses.
Dimensions: See dimensions
illustration.
Ratings:
Volts: — 1000Vac.
Amps: — 50-1400A
IR: — 150kA (Est. 300kA) RMS Sym.
Agency Information: CE, Designed and tested to IEC
60269: Part 4, UL Recognized.
Electrical Characteristics
Total clearing I2t
The total clearing I2t at
rated voltage and at power
factor of 15% are given in
the electrical
characteristics. For other
voltages, the clearing I2t is
found by multiplying by
correction factor, K, given
as a function of applied
working voltage, Eg, (rms).
Arc Voltage
This curve gives the peak
arc voltage, UL, which may appear across the fuse
during its operation as a
function of the applied
working voltage Eg, (rms) 5at a power factor of 15%.
Power Losses
Watts loss at rated current 1,0is given in the electrical
characteristics. The curve
allows the calculation of
the power losses at load
currents lower than the
rated current. The
correction factor, Kp, is
given as a function of the
RMS load current, I , in %
b
of the rated current.
Features and Benefits
• Excellent DC performance
• Low arc voltage and low energy let-through (I2t)
• Low watts loss
• Superior cycling capability
Typical Applications
• DC common bus
• DC drives
• Power converters/rectifiers
• Reduced voltage starters
For Other Voltage Ratings in This Body Style
• See pages 124 (690V/700V) and 162 (1250V/1300V)
Dimensions (mm)
Catalog Numbers
**Overall length is 90mm, for all other fuses the overall length is 75mm.
• Watts loss provided at rated current. • Microswitch ordered separately. See accessories on page 185-186. • For fuse curves see pages 152 and 153.