Description: Square body DIN
43 620 blade style high speed
fuses.
Dimensions: See dimensions
illustration.
Ratings:
Volts:— 690Vac (IEC)
— 700Vac (UL)
Amps:— 40-1000A IR:— 200kA RMS Sym.
Agency Information: CE, Designed and tested to IEC
60269: Part 4, UL Recognized.
Electrical Characteristics
Total Clearing I2t
The total clearing I2t at
rated voltage and at power
factor of 15% are given in
the electrical characteris-
tics. For other voltages,
the clearing I2t is found by
multiplying by correction
factor, K, given as a func-
tion of applied working
voltage, Eg, (rms).
Arc Voltage 1.4
1.2arc voltage, U , which may
This curve gives the peak
L9appear across the fuse 8
during its operation as a
function of the applied
working voltage, Eg, (rms) 5at a power factor of 15%.
Power Losses
Watts loss at rated current is given in the electrical
characteristics. The curve
allows the calculation of the power losses at load
currents lower than the rated current. The correc-tion factor, Kp, is given as a function of the RMS load 0.2current, Ib, in % of the
rated current.
Features and Benefits
• Excellent dc performance • Low arc voltage and low energy let-through (I2t)
• Low watts loss • Superior cycling capability
Typical Applications
• DC common bus • DC drives • Power converters/rectifiers
• Reduced voltage starters
Dimensions (mm)
Rated Current
The rated current of this fuse range has been given with
copper conductors that have a current density of 1.3 A/mm2(IEC 60269-4). For conductor cross section according to IEC
60269-1, the fuses must be derated. Please contact Cooper
Bussmann for application assistance.