Eaton’s BussmannTM series LimitronTM advanced
protection Class T current -limiting, fast-acting
fuses.
Specifications:
Ratings
Volts
300 Vac (1-10 A)
300 Vac, 160 Vdc (15-600 A)
300 Vac, 170 Vdc (700-1200 A)
Amps — 1-1200 A
IR
200kA Vac RMS Sym.
20kA Vdc (15-600 A)
100kA Vdc (700-1200 A)
Dimensions – in
Agency Information
UL® Listed, Std. 248-15, Class T, Guide JDDZ,
File E4273
CSA® Certified, C22.2 No. 248.15, Class 1422-
02, File 53787
CE
RoHS compliant
Features:
Provides 10X better current limitation to help
prevent equipment damage caused by short-
circuit events.
200 kA interrupting rating complies with NEC®Section 110.9 for today’s large capacity systems.
Fast-acting fuse helps prevent equipment
damage caused by short-circuit events.
Small, space-saving fuses provide a high
degree of current limitation on short-circuits for
excellent component protection.
Ideal for critical industrial or commercial
applications that have specific current limitation
requirements.
Recommended fuse blocks*
* For additional information, see data. sheet no. 1115.
Custom designs
Printed circuit board versions available up to 60 amps. Consult your
Bussmann series product representative details.
JJN-XXL Dimensions - in
The JJN-XXL and JJN-XXLS products are UL Component Recognized
under Guide JFHR2, File E56412. Contact your Bussmann series
product representative for RoHS status.
Time-current curves - average melt
Current-limitation curves
RMS SYMMETRICAL CURRENT IN AMPS A-B = ASYMMETRICAL AVAILABLE PEAK (2.3 X SYM RMS AMPS)