FRS-R 250V RK5 0.1-60A
    发布时间: 2023-09-14 11:06    



                    

Description: Advanced protection, energy efficient Class RK5 dual element, current-limiting, time-delay fuses with optional open fuse indication on select ratings.

Time-delay – 10 seconds (minimum) at 500% of rated current (8 seconds for 110-30A sizes).


Catalog Symbol: FRN-R-(amp) (non-indicating) FRN-R-(amp)ID (indicating)


Ratings:

Volts — 250Vac, 125Vdc Amps — 110-60 Amps

IR — 200kA Vac RMS Sym. — 20kA Vdc


Agency Information:

CE, UL Listed, Std. 248-12, Class RK-5, Guide JDDZ, File E4273

CSA Certified, C22.2 No. 248.12, Class 1422-02, File 53787


Catalog Numbers (amps) — Non-indictaing fuses

* Open fuse indication available by inserting the sufix “ID.” E.g., FRN-R-15ID.


Carton Quantity and Weight


Time-Current Curves - Average Melt 8 to 60 Amps


Dimensions - in


Features:

  • Provides motor overload, ground fault and short-circuit protection

  • Helps protect motors against burnout from overloads

  • Helps protect motors against burnout from single-phasing

  • on three-phase systems

  • Simplifies and improves blackout prevention

  • (selective coordination)

  • Dual-element fuses can be applied in circuits subject to

  • temporary motor overloads and surge currents to provide both high performance short-circuit and overload protection

  • The overload element provides protection against low level overcurrent of overloads and will hold an overload which is five times greater than the ampere rating of the fuse for a minimum of ten seconds.

Recommended Fuse Blocks

For additional information on the 250 volt fuse blocks, see Data Sheets # 1110 (R250), # 1112 (H250).

Fuse Reducers For Class R Fuses

For additional information on Class R fuse reducers, see Data Sheet # 1118.


Current-Limitation Curves